Your present location:HomeProductsDin Rail Power Supply / DG-360 series
  • Product No.: DG-360 series

Universal AC input range(85~264Vac)

Support 1+1 or N+1 redundant systemsuggest to use redundancy modules.

Built-in active PFC,PF>0.95

High efficiency up to 93%

Built-in current sharing function

Built-in current limiting circuit

Output protections:OVP/OLP/SCP/OTP

Wide operating ambient temp (-25~70℃)

150%(540W) peak load capacity

Excellent Partial Load Efficiency

Built-in DC OK relay contact

Can be installed on TS-35/7.5 or TS-35/15

100% full load burn-in test

Suitable for critical applications

Ultra-slim, 50mm width

Free air convection

3 years warranty 

MODEL

DG-360-24

DG-360-36

DG-360-48

OUTPUT

DC Output

24V

36V

48V

Rated Current

15A

10A

7.5A

CurrentRange     Note 1

0~15A

0~10A

0~7.5A

Ripple and Noise 

Note 2

0~70

≤240mV

≤240mV

≤480mV

-25

≤480mV

≤480mV

≤720mV

Voltage ADJ.  Range

24~28V

34~37.5V

48~56V

Voltage Accuracy

±3.0%

Line Regulation

±0.5%

Load Regulation

±1.0%

Set-up Time

<3S@230Vac  

Hold up Time

≥20mS(230Vac input, Full load)

Temperature Coefficient

±0.03%/

Overshoot and Undershoot

<5.0%

INPUT

VoltageRange  

85Vac~264Vac

FrequencyRange

47Hz~63Hz

Power Factor (typical)

0.99/110Vac     0.95/230Vac   full load

Efficiency ( Typical) at 230Vac

≥93%

≥92.5%

≥92.5%

AC Current (max.)

<5A/100Vac      <2.5A/230Vac

Inrush Current (Typical)

<20A/110Vac<40A/230Vac   Cold start

Leakage Current

Input—output:<0.25mA     Input—PG:<3.5mA

PROTECTION

Over Load

110%~150% of rated current, Constant current limiting for some time(150% of rated current, last 3S) then PS stop working for 7S,after 7S,if the load <=rated current, PS will work normally, auto recovery

Over voltage

29~33V, constant voltage,

Auto recovery

39~43V, constant voltage

Auto recovery

58~63V, constant voltage

Auto recovery

Over temperature

115±5℃, detect on heat sink of power transistor; shut down O/P, auto recovery after temperature goes down.

Short Circuit

Long-term mode, auto recovery

ENVIRONMENT

Operating amb. Temp. & Hum.

-25~70;  20%~90%RH  No condensing

Storage Temp. & Hum.

-40~85;  5%~95%RH  No condensing

SAFETY &EMC

Note 3

Safety Standards

meet UL508, UL60950, EN60950

Withstand Voltage

Primary-Secondary:3.0KVac; 10mA .Primary-PG:2.5KVac; 10mA. Secondary-PG:0.5KVac20mA.

Isolation Resistance

100M ohms

EMC Emission

Compliance to EN55022, EN55024, FCC PART 15  Class B

Harmonic Current

Compliance to EN61000-3-2, CLASS A

EMC Immunity

Compliance to EN61000-4-2,3,4,5,6,8,11; heavy industry level

OTHERS

MTBF (MIL-HDBK-217F)

More than 300,000Hrs (25, Full load)

Dimension   (W*H*D)

50*124*127mm

Packing

12pcs/CTN, 11Kgs/CTN, 0.04cbm

Cooling method

Cooling by free air convection

 

Additional function

Power boost

150% of rated current

Parallel function

support

NOTE

1. All parameters NOT specially mentioned are measured at rated input, rated load and 25 of ambient temperature.

2. Measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1 uF & 10uF parallel capacitor.

3. The SPS is considered a component which will be installed into final equipment. We cannot guarantee that the final equipment will meet EMC directives, Final product manufactures must be re-confirm that their product meets EMC directives